| 20 kV Transition Joints CHMP (H) 3-1 |  |
| heat shrink technique
|
for metallized paper screened cable
to 3 single-core polymeric cable |
| Cable Type |
Joint Type |
Cross Section for 12 kV (mm²) |
Ø min. over Insulation (mm) |
Ø max. over Connector (mm) |
max. Connector- length (mm) |
N(A)HKBA to N(A)2XS(F)2Y |
CHMP(H) 3-1 24 kV 16-35 |
16 – 35 |
12,6 |
15 |
100 |
| CHMP(H) 3-1 24 kV 35-70 |
35 – 70 |
17,3 |
25 |
110 |
| CHMP(H) 3-1 24 kV 95-240 |
95 - 240 |
19,9 |
33 |
150 |
| CHMP(H) 3-1 24 kV 185-300 |
185 - 300 |
23,1 |
40 |
160 |
Characteristics
The stress-control is made by silicone slip-on elements.
The insulation is made by heat shrink tubes.
The joint combines save installation with slip-on elements
and the flexibility and efficiency of heat shrink technique.
The joint allows connections between different crosssections
and different cabledesigns.
Construction
The joint consists of silicone stress-control elements,
filling tape, oil-resisting heat shrink tubes, conductive heat
shrink tubes and spreader cap, insulating tubes, tubes
with conductive outer layer, screen of copper mesh and
outer protection tube.
Screw or compression connectors are not included.
|
Tests
The termination is tested according to CENELEC HD
629.2 and meets the requirements of all essential
international regulations. |
|
|
 |
|