| 10 / 30 kV Straight Joints CHM |  |
heat shrink technique for single-core polymeric cable |
| 10 (12) kV-Joints |
| Joint Type |
Cross Section (mm²) |
Ø min. over Insulation (mm) |
Ø max. over Connector (mm) |
max. Connectorlengths (mm) |
| CHM 12 kV 35-95 |
35 – 95 |
12,6 |
25 |
135 |
| CHM 12 kV 95-240 |
95 – 240 |
17,3 |
33 |
145 |
| CHM 12 kV 150–300 |
150 – 300 |
19,9 |
40 |
220 |
| 20 (24) kV-Joints |
| Joint Type |
Cross Section (mm²) |
Ø min. over Insulation (mm) |
Ø max. over Connector (mm) |
max. Connectorlengths (mm) |
| CHM 24 kV 10-35 |
10 – 35 |
12,6 |
20 |
100 |
| CHM 24 kV 50-150 |
50 – 150 |
17,3 |
25 |
125 |
| CHM 24 kV 70-240 |
70 – 240 |
19,9 |
33 |
145 |
| CHM 24 kV 150–300 |
150 – 300 |
23,1 |
40 |
220 |
| 30 (36) kV-Joints |
| Joint Type |
Cross Section (mm²) |
Ø min. over Insulation (mm) |
Ø max. over Connector (mm) |
max. Connectorlengths (mm) |
| CHM 36 kV 35-70 |
35 – 70 |
19,9 |
20 |
100 |
| CHM 24 kV 70-150 |
70 – 150 |
23,1 |
25 |
135 |
| CHM 36 kV 150–300 |
150 – 300 |
27,3 |
35 |
220 |
Application
The heat shrink joint type CHM is suitable for single-core
polymeric cables up to 30 kV.
It allows connections between different cross-sections and
different cable-designs.
|
Construction
The joint consists of silicone stress-control elements,
filling tape, insulating tubes, tubes with conductive outer
layer, screen of copper mesh and outer protection tube.
The installation is easy and time-saving.
Tests
The joint is tested according to CENELEC HD 629.2
and meets the requirements of all essential international
regulations. |
|