| 1 kV Branch Joint HSM |  |
| resin technique |
| Main Cable according to DIN/TGL | Branch Cable according to DIN/TGL |
| Type | Cross Section (mm²) | Max. Diameter-Ø | Type | Cross Section (mm²) | Max. Diameter-Ø |
| N(A)YY, N(A)Y2Y, NA2XY, NA2X2Y | 4 x 35
to 4 x 185 | 47 mm | N(A)YY, N(A)Y2Y, NA2XY, NA2X2Y | 4 x 16 to 4 x 70 | 32 mm |
Joint Box Type |
Dimensions (mm) |
Joint Box Volume |
Resin Net Weight |
Kit Gross Weight |
| a = Ø |
b |
c |
| HSM 280/140 |
140 |
230 |
280 |
2.300 cm³ |
2,4 kg |
3,5 kg |
Handling
By few and simple mounting steps a fast and operatorsafe
assembly of the joint box is ensured.
Application
The joint box is suitable for use with all available cable
ring connectors.
Quality
The joint box is system-tested according to VDE 0278 part
of 1 and 3 respectively hp 623. Our cast resins fulfill the
requirements of VDE 0291 part of 2 respectively hp 631.1.
By application of the quality management system in
accordance with DIN EN ISO 9001:2000 the quality of our
products is guaranteed. |
Specification
- two-part, transparent shell
- PUR and hardener in tins or alternatively in doublechamber
bags
- stirring spatula (for tins)
- sealings
- emery cloth
- protection gloves
- installation instructions
|
|
|
 |
|